Product Details:
Payment & Shipping Terms:
|
Current: | 100~4000A | High Voltage: | 24KV |
---|---|---|---|
Low Voltage: | 400V | Rated Capacity: | 30~2000KVA |
Sound Level: | Sound Level | ||
Highlight: | oil immersed distribution transformer,packaged transformer substation |
POWER DISTRIBUTION SUBSTATION / COMPACT / OUTDOOR 24KV
YBT12-24 Series Combined Substation is researched and developed by our company in order to satisfy the need of city net construction. It has compact structure, strong whole set, safe and reliable operation, convenient maintenance, beautiful appearance. It is widely used in outdoor power supply fields such as high buildings, residential zone, station, wharf, port, park, marketplace and factory and mining, etc. The product can not only be used in a closing net for power distribution but also in radial grid for terminal power supply. The product has novel structure, reliable performance, excellent in quality and technical characteristic reachs to the national advanced level.
a. The frame of substation is made of channel steel and angle steel, it is tough enough mechanically and rigidly.
b. Materials of the enclosure can be cold rolled steel plate, stainless steel plate, aluminum alloy plate, composite color plate, or cement plate strength by glass fiber.
c. Steel plates are used to isolate each bay, and lighting device has provided in the substation.
d. The roof is double-decked structure, which can prevent the heat radiation from increasing indoor temperature and have good ventilation effect at the same time.
e. There's an automatic air exhausting device at the top of transformer room to control the temperature.
f. The enclosure can be painted in many colors to coordinate with ambient environment.
Items | Unit | Data | |
HV unit |
Rated Voltage | kV | 24 |
Rated Frequency | Hz | 50 | |
Rated Main Busbar Current | A | 630 | |
1min Power Frequency Withstand Voltage To Earth, Between Phases/to open gap | kV | 50/65 | |
Lightning Impulse Withstand Voltage to Earth and Between Phases/ to open gap | kV | 95/110 | |
Rated Short-time Withstand Current | kA/s | 25/2 | |
Rated Peak Withstand Current | kA | 63 | |
Rated Short-time Making Current | kA | 63 | |
Fuse Breaking Current | kA | 31.5 | |
Circuit Breaker Breaking Current | kA | 25 | |
LV unit |
Rated Voltage | V | 400 |
Main Circuit Rated Current | A | 100~4000 | |
Rated Limit Short-circuit Breaking Capacity | kA | 80 | |
Rated Operating Short-circuit Breaking Capacity | kA | 50(65) | |
Rated Short-time Withstand Current | kA/1s | 50(65) | |
Branch Current, Compensation Capacity | According to users’ requirements | ||
Transformer |
Rated Capacity | kVA | 30~2000 |
Resistance Voltage | % | 4/4.5 | |
Tapping Range | % | ±2×2.5 ±5 | |
Connected Group | Y,yn0 D,yn11 | ||
Case body | Protection Level | IP23 | |
Sound level | dB | ≤50 |
Contact Person: Ms. Lian Huanhuan
Tel: +86-13858385873
Fax: 86-574-87911400